On-line Double Conversion 3 Phase UPS 15KVA - 200KVA
Taurus Series
Features

Features

  • Online Double Conversion technology with DSP control
  • Input power factor 0.99 at 10% load
  • Output power factor 0.9
  • High output efficiency
  • Advanced control with Adaptive Feedforward Cancellation (AFC) technology for very low harmonic distortion
  • Low input current distortion (THDi < 1%)
  • An estimated battery runtime indicate on the 7' LCD in the event of power outage
  • Front access make maintenance and replacement easily
  • Parallel redundant operation up to 4 units
  • Flexible battery quantity configuration
  • Full connectivity - USB, RS232, Modbus, Dry contact and intelligent slot
  • Design for environment. Use more than 60% recyclable and renewable source materials
  • Space-saving compact design
Taurus Pro 15K-20K
Nominal Power(KVA) 15/20
Nominal Power(KW) 13.5/18
Input
Nominal Voltage Three phase 3 x 380/400/415 VAC (4 wires: 3 phases + N + E)
Input Voltage Range +15% / -20%
Frequency 50/60Hz ±5%
Input Current Total Harmonic Distortion THDi 100% load < 1.5%
50% load < 2.5%
10% load < 6.0%
Power Factor 1.0 (at any load condition)
Inverter
Nominal Voltage Three phase 3 x 380V, 3x400V or 3 x 415V (4 Wires, 3phases + N + E)
Regulation Steady State: ±1%. Dynamic State: ±2% (Load Variations 100 - 0 - 100%)
Frequency 50/60Hz synchronised ±4%. With mains absent ±0.05%
Siew Rate ±1 Hz/s
Wave Form Pure Sinewave
Output Voltage Total Harmonic Distortion Linear load: THDv < 0.5%, non-linear load: THDv < 1.5%
Phase Displacement 120° ±1% (balanced load), 120° ±2% (un-balanceds load)
Dynamic Recovery Time 10ms at 98%
Permissible Overload - Transfer / Shutdown 100-125% : 10mins, 125-135% : 15mins, 135-150% : 1min, > 150% : immediate
Permissible Crest Factor 3.4 to 1
Battery
Battery Quantity 31+31, 3 poles postive, midpoint, negetive
Battery Type 12V, Sealed Lead Acid
Battery Charging 4-5 Hours to 90% capacity and user configurrable current depending on battery capacity
Battery Float Voltage +423 / -423 @ 20°
Battery Test Build-in automatic
Taurus Pro 30K/40K/60K
Nominal Power(KW) 30K/40K/60K
Nominal Power(KW) 27/36/54
Input
Nominal Voltage Three phase 3 x 380/400/415 VAC (4 wires: 3 phases + N + E)
Input Voltage Range +15% / -20%
Frequency 50/60Hz ±5%
Input Current Total Harmonic Distortion THDi 100% load < 1.0%
50% load < 2.0%
10% load < 6.0%
Power Factor 1.0 (at any load condition)
Inverter
Nominal Voltage Three phase 3 x 380V, 3x400V or 3 x 415V (4 Wires, 3phases + N + E)
Regulation Steady State: ±1%. Dynamic State: ±2% (Load Variations 100 - 0 - 100%)
Frequency 50/60Hz synchronised ±4%. With mains absent ±0.05%
Siew Rate ±1 Hz/s
Wave Form Pure Sinewave
Output Voltage Total Harmonic Distortion Linear load: THDv < 0.5%, non-linear load: THDv < 1.5%
Phase Displacement 120° ±1% (balanced load), 120° ±2% (un-balanceds load)
Dynamic Recovery Time 10ms at 98%
Permissible Overload - Transfer / Shutdown 100-125% : 10mins, 125-135% : 15mins, 135-150% : 1min, > 150% : immediate
Permissible Crest Factor 3.2 to 1
Battery
Battery Quantity 31+31, 3 poles postive, midpoint, negetive
Battery Type 12V, Sealed Lead Acid
Battery Charging 4-5 Hours to 90% capacity and user configurrable current depending on battery capacity
Battery Float Voltage +423 / -423 @ 20°
Battery Test Build-in automatic
Taurus Pro 80K
Nominal Power(KVA) 80K
Nominal Power(KW) 72
Input
Nominal Voltage Three phase 3 x 380/400/415 VAC (4 wires: 3 phases + N + E)
Input Voltage Range +15% / -20%
Frequency 50/60Hz ±5%
Input Current Total Harmonic Distortion THDi 100% load < 1.0%
50% load < 2.0%
10% load < 6.0%
Power Factor 1.0 (at any load condition)
Inverter
Nominal Voltage Three phase 3 x 380V, 3x400V or 3 x 415V (4 Wires, 3phases + N + E)
Regulation Steady State: ±1%. Dynamic State: ±2% (Load Variations 100 - 0 - 100%)
Frequency 50/60Hz synchronised ±4%. With mains absent ±0.05%
Siew Rate ±1 Hz/s
Wave Form Pure Sinewave
Output Voltage Total Harmonic Distortion Linear load: THDv < 0.5%, non-linear load: THDv < 1.5%
Phase Displacement 120° ±1% (balanced load), 120° ±2% (un-balanceds load)
Dynamic Recovery Time 10ms at 98%
Permissible Overload - Transfer / Shutdown 100-125% : 10mins, 125-135% : 15mins, 135-150% : 1min, > 150% : immediate
Permissible Crest Factor 2.8 to 1
Battery
Battery Quantity 31+31, 3 poles postive, midpoint, negetive
Battery Type 12V, Sealed Lead Acid
Battery Charging 4-5 Hours to 90% capacity and user configurrable current depending on battery capacity
Battery Float Voltage +423 / -423 @ 20°
Battery Test Build-in automatic
Taurus Pro 100K/120K
Nominal Power(KVA) 100K/120K
Nominal Power(KW) 90/108
Input
Nominal Voltage Three phase 3 x 380/400/415 VAC (4 wires: 3 phases + N + E)
Input Voltage Range +15% / -20%
Frequency 50/60Hz ±5%
Input Current Total Harmonic Distortion THDi 100% load < 1.5%
50% load < 2.0%
10% load < 6.0%
Power Factor 1.0 (at any load condition)
Inverter
Nominal Voltage Three phase 3 x 380V, 3x400V or 3 x 415V (4 Wires, 3phases + N + E)
Regulation Steady State: ±1%. Dynamic State: ±2% (Load Variations 100 - 0 - 100%)
Frequency 50/60Hz synchronised ±4%. With mains absent ±0.05%
Siew Rate ±1 Hz/s
Wave Form Pure Sinewave
Output Voltage Total Harmonic Distortion Linear load: THDv < 0.5%, non-linear load: THDv < 1.5%
Phase Displacement 120° ±1% (balanced load), 120° ±2% (un-balanceds load)
Dynamic Recovery Time 10ms at 98%
Permissible Overload - Transfer / Shutdown 100-125% : 10mins, 125-135% : 15mins, 135-150% : 1min, > 150% : immediate
Permissible Crest Factor 3.2 to 1
Battery
Battery Quantity 31+31, 3 poles postive, midpoint, negetive
Battery Type 12V, Sealed Lead Acid
Battery Charging 4-5 Hours to 90% capacity and user configurrable current depending on battery capacity
Battery Float Voltage +423 / -423 @ 20°
Battery Test Build-in automatic
Taurus Pro 160K/200K
Nominal Power(KVA) 160K/200K
Nominal Power(KW) 144/180
Input
Nominal Voltage Three phase 3 x 380/400/415 VAC (4 wires: 3 phases + N + E)
Input Voltage Range +15% / -20%
Frequency 50/60Hz ±5%
Input Current Total Harmonic Distortion THDi 100% load < 1.5%
50% load < 2.0%
10% load < 6.0%
Power Factor 1.0 (at any load condition)
Inverter
Nominal Voltage Three phase 3 x 380V, 3x400V or 3 x 415V (4 Wires, 3phases + N + E)
Regulation Steady State: ±1%. Dynamic State: ±2% (Load Variations 100 - 0 - 100%)
Frequency 50/60Hz synchronised ±4%. With mains absent ±0.05%
Siew Rate ±1 Hz/s
Wave Form Pure Sinewave
Output Voltage Total Harmonic Distortion Linear load: THDv < 0.5%, non-linear load: THDv < 1.5%
Phase Displacement 120° ±1% (balanced load), 120° ±2% (un-balanceds load)
Dynamic Recovery Time 10ms at 98%
Permissible Overload - Transfer / Shutdown 100-125% : 10mins, 125-135% : 15mins, 135-150% : 1min, > 150% : immediate
Permissible Crest Factor 3.0 to 1
Battery
Battery Quantity 31+31, 3 poles postive, midpoint, negetive
Battery Type 12V, Sealed Lead Acid
Battery Charging 4-5 Hours to 90% capacity and user configurrable current depending on battery capacity
Battery Float Voltage +423 / -423 @ 20°
Battery Test Build-in automatic

Technical specifications are subject to change without notice.