Arena Series
6 kVA – 100 kVA Rack Independent
Hot-Swappable True Double Conversion Modular UPS
Galleon Pro Rackmount Series
Features

Features

  • Standard 19” form factor with tower/rack convertible design
  • Rack independent, hot swappable, field upgradeable and serviceable module UPS
  • True double-conversion On-line UPS
  • DSP technology guarantees high performance
  • Output power factor 1.0
  • Active power factor correction in all phases
  • Independent built-in bypass for each UPS module
  • 50/60Hz frequency converter mode
  • ECO mode operation for energy saving (ECO)
  • Emergency power off function (EPO)
  • SNMP and USB for multiple communications
  • Adjustable battery numbers for extended runtime and flexible power demands
  • Cold start capability
  • Generator compatible
  • Customizable system to meet various application
Arena 10K
Phase 1 Phase In / 1 Phase Out
Capacity 10 kVA / 10kW
No. Parallel Units Capability Up to 10
Topology Online Double Conversion
Input
Nominal Voltage 208 / 220 / 230 / 240 VAC (1Ph + L + N)
Voltage Range 110-300 VAC ± 3% @ 50% load
176-276 VAC ± 3% @ 100% load
Frequency Range 40~70Hz
Power Factor ≥ 0.99 @ 100% load
Harmonic Distortion (THDi) < 4% @ 100% linear load
Output
Output Voltage 208* / 220 / 230 / 240 VAC (1Ph + L + N)
AC Voltage Regulation
(Steady. Mode)
± 1%
Current Crest Ratio 3:1
Frequency Range (Synchronized) 46Hz~54Hz or 56Hz~64Hz
Frequency Range (Battery Mode) 50Hz ± 0.1Hz / 60Hz ± 0.1 Hz
Overload Capacity 1 hour for 110%, 10 mins for 125%, 1min for 15%, 200ms for > 150%
Harmonic Distortion (THDv) ≤ 2% (Linear load)
≤ 3% (Non-linear load)
Efficiency
AC Mode 93.5%
Eco Mode 97.0%
Battery Mode 92.0% @ Full load
92.5% @ Peak
Battery & Charger
Battery Type 12V Sealed Lead Acid Maintenance Free (SLA)
Nominal Voltage ± 192V (12V x 32pcs)
Maximum Voltage ± 240V (12V x 40pcs)
Minimun Voltage ± 192V (12V x 32pcs)
Charging Voltage ± 218
Boost Charging Voltage 2.35V / Cell
Typical Recharge Time 9 hours to recover to 90% capacity after full discharge
Maximum Charging Current ± 4A
Arena 3C - 10K
Phase 3 Phase In / 1 Phase Out
Capacity 10 kVA / 10kW
No. Parallel Units Capability Up to 10
Topology Online Double Conversion
Input
Nominal Voltage 3 x 360 / 380 / 400 / 415 VAC (3Ph + N + PE)
Voltage Range 190~520VAC @ 50% load
305~478VAC @ 100% load
Frequency Range 40~70Hz
Power Factor ≥ 0.99 @ 100% load
Harmonic Distortion (THDi) < 4% @ 100% linear load
Output
Output Voltage 208* / 220 / 230 / 240 VAC (1Ph + L + N)
AC Voltage Regulation
(Steady. Mode)
± 1%
Current Crest Ratio 3:1
Frequency Range (Synchronized) 46Hz~54Hz or 56Hz~64Hz
Frequency Range (Battery Mode) 50Hz ± 0.1Hz / 60Hz ± 0.1 Hz
Overload Capacity 1 hour for 110%, 10 mins for 125%, 1min for 15%, 200ms for > 150%
Harmonic Distortion (THDv) ≤ 2% (Linear load)
≤ 3% (Non-linear load)
Efficiency
AC Mode 94%
Eco Mode 97.0%
Battery Mode 92.5% @ Full load
93% @ Peak
Battery & Charger
Battery Type 12V Sealed Lead Acid Maintenance Free (SLA)
Nominal Voltage ± 192V (12V x 32pcs)
Maximum Voltage ± 240V (12V x 40pcs)
Minimun Voltage ± 192V (12V x 32pcs)
Charging Voltage ± 218
Boost Charging Voltage 2.35V / Cell
Typical Recharge Time 9 hours to recover to 90% capacity after full discharge
Maximum Charging Current ± 4A
Arena 3P - 10K
Phase 3 Phase In / 3 Phase Out
Capacity 10 kVA / 10kW
No. Parallel Units Capability Up to 10
Topology Online Double Conversion
Input
Nominal Voltage 3 x 360 / 380 / 400 / 415 VAC (3Ph + N + PE)
Voltage Range 190~520VAC @ 50% load
305~478VAC @ 100% load
Frequency Range 40~70Hz
Power Factor ≥ 0.99 @ 100% load
Harmonic Distortion (THDi) < 4% @ 100% linear load
Output
Output Voltage 3 x 360 / 380 / 400 / 415 VAC (3Ph + N + PE)
AC Voltage Regulation
(Steady. Mode)
± 1%
Current Crest Ratio 3:1
Frequency Range (Synchronized) 46Hz~54Hz or 56Hz~64Hz
Frequency Range (Battery Mode) 50Hz ± 0.1Hz / 60Hz ± 0.1 Hz
Overload Capacity 1 hour for 110%, 10 mins for 125%, 1min for 15%, 200ms for > 150%
Harmonic Distortion (THDv) ≤ 2% (Linear load)
≤ 3% (Non-linear load)
Efficiency
AC Mode 94%
Eco Mode 97.0%
Battery Mode 93.0% @ Full load
93.5% @ Peak
Battery & Charger
Battery Type 12V Sealed Lead Acid Maintenance Free (SLA)
Nominal Voltage ± 192V (12V x 32pcs)
Maximum Voltage ± 240V (12V x 40pcs)
Minimun Voltage ± 192V (12V x 32pcs)
Charging Voltage ± 218
Boost Charging Voltage 2.35V / Cell
Typical Recharge Time 9 hours to recover to 90% capacity after full discharge
Maximum Charging Current ± 4A

Technical specifications are subject to change without notice.
*When single phase output set to 208VAC, the output power shall be de-rated to 90%.