Preloader
Galleon Pro III 3P Series
Online Double Conversion
60KVA/KW-200KVA/KW 3
Phase in / 3 Phase Out UPS
Galleon Pro 3P/3P Series
Features

Features

  • True Online Double Conversion Sinewave UPS
  • Modular Design which pluggable during maintenance decrease MTTR
  • Output power factor = 1.0
  • Active power factor correction for all input phases
  • 50Hz/60Hz frequency converter mode
  • ECO mode operation for energy saving
  • 7” LCD colour Touch Screen with Mimic Flow
  • Adjustable battery quantity design
  • Dual input for flexible configuration
  • 3-stage charging design to optimize battery performance
  • Parallel operation up to 4 units with common battery system
  • Power walk-in function
  • Generator Compatible
Galleon Pro III 10K
Phase 1 Phase in / 1Phase out;
3 Phase in / 1 Phase out;
3 Phase in / 3 Phase out
Capacity 10kVA / 10kW
Input
Nominal Voltage One Phase 220 / 230 / 240V (2 wires, 1 Ph + N + E)
Three Phase 3 x 380 / 400 / 415V (4Wires, 3phases + N + E)
Voltage Range 190-520 VAC (3-Phase) at 50% load
305-478 VAC (3-Phase) at 100% load
Frequency Range 46Hz~54Hz or 56Hz~64Hz
Power Factor >0.99 @ 100% load
Output
Output Voltage One Phase 220 / 230 / 240V (2 wires, 1 Ph + N + E)
Three Phase 3 x 360* / 380 / 400 / 415V (4Wires, 3phases + N + E)
AC Voltage Regulation (Batt. Mode) ± 1%
Frequency Range (Sync. Range) 46Hz~54Hz or 56~64Hz
Frequency Range (Batt. Mode) 46Hz~54Hz ± 1% or 56~64Hz ± 1%
Current Crest Ratio 3:1 (max)
Harmonic Distortion < 2% THD (Linear load)
< 5% THD (Non-linear load)
Transfer Time - AC Mode to Battery Mode 0ms
Transfer Time - Inverter to Bypass 0ms
Waveform (Battery mode) Pure Sinewave
Overload Capability 100-110% for 60mins; 111-125% for 10mins,
126-150% for 1min; >150% immediately
Efficiency
AC Mode 95.5%
ECO Mode 98.5%
Battery Mode 94.5%
Battery - Standard Model
Battery Type 12V9AH
Quantity (10+10) pcs
Typical Recharge Time 9 Hours recover to 90% capacity
Charging Current (max.) 1A-12A (Adjustable)
Charging Voltage ± 136VDC ±10%
Battery - Extended Runtime Model
Battery Type Depending on the capacity of external batteries
Quantity 10+10pcs
Charging Current (max.) 1A-12A (Adjustable)
Charging Voltage ± 13.65V x N (N=16~20)
Galleon Pro III 15K
Phase 1 Phase in / 1Phase out;
3 Phase in / 1 Phase out;
3 Phase in / 3 Phase out
Capacity 15kVA / 15kW
Input
Nominal Voltage One Phase 220 / 230 / 240V (2 wires, 1 Ph + N + E)
Three Phase 3 x 380 / 400 / 415V (4Wires, 3phases + N + E)
Voltage Range 190-520 VAC (3-Phase) at 50% load
305-478 VAC (3-Phase) at 100% load
Frequency Range 46Hz~54Hz or 56Hz~64Hz
Power Factor >0.99 @ 100% load
Output
Output Voltage One Phase 220 / 230 / 240V (2 wires, 1 Ph + N + E)
Three Phase 3 x 360* / 380 / 400 / 415V (4Wires, 3phases + N + E)
AC Voltage Regulation (Batt. Mode) ± 1%
Frequency Range (Sync. Range) 46Hz~54Hz or 56~64Hz
Frequency Range (Batt. Mode) 46Hz~54Hz ± 1% or 56~64Hz ± 1%
Current Crest Ratio 3:1 (max)
Harmonic Distortion < 2% THD (Linear load)
< 5% THD (Non-linear load)
Transfer Time - AC Mode to Battery Mode 0ms
Transfer Time - Inverter to Bypass 0ms
Waveform (Battery mode) Pure Sinewave
Overload Capability 100-110% for 60mins; 111-125% for 10mins,
126-150% for 1min; >150% immediately
Efficiency
AC Mode 95.5%
ECO Mode 98.5%
Battery Mode 94.5%
Battery - Standard Model
Battery Type 12V7AH
Quantity (16+16) pcs
Typical Recharge Time 9 Hours recover to 90% capacity
Charging Current (max.) 1A-12A (Adjustable)
Charging Voltage ± 218VDC ±10%
Battery - Extended Runtime Model
Battery Type Depending on the capacity of external batteries
Quantity 32 (16+16pcs) ~ 40(20+20pcs) Adjustable
Charging Current (max.) 1A-12A (Adjustable)
Charging Voltage ± 13.65V x N (N=16~20)
Galleon Pro III 20K
Phase 1 Phase in / 1Phase out;
3 Phase in / 1 Phase out;
3 Phase in / 3 Phase out
Capacity 20kVA / 20kW
Input
Nominal Voltage One Phase 220 / 230 / 240V (2 wires, 1 Ph + N + E)
Three Phase 3 x 380 / 400 / 415V (4Wires, 3phases + N + E)
Voltage Range 190-520 VAC (3-Phase) at 50% load
305-478 VAC (3-Phase) at 100% load
Frequency Range 46Hz~54Hz or 56Hz~64Hz
Power Factor >0.99 @ 100% load
Output
Output Voltage One Phase 220 / 230 / 240V (2 wires, 1 Ph + N + E)
Three Phase 3 x 360* / 380 / 400 / 415V (4Wires, 3phases + N + E)
AC Voltage Regulation (Batt. Mode) ± 1%
Frequency Range (Sync. Range) 46Hz~54Hz or 56~64Hz
Frequency Range (Batt. Mode) 46Hz~54Hz ± 1% or 56~64Hz ± 1%
Current Crest Ratio 3:1 (max)
Harmonic Distortion < 2% THD (Linear load)
< 5% THD (Non-linear load)
Transfer Time - AC Mode to Battery Mode 0ms
Transfer Time - Inverter to Bypass 0ms
Waveform (Battery mode) Pure Sinewave
Overload Capability 100-110% for 60mins; 111-125% for 10mins,
126-150% for 1min; >150% immediately
Efficiency
AC Mode 95.5%
ECO Mode 98.5%
Battery Mode 94.5%
Efficiency
AC Mode 95.5%
ECO Mode 98.5%
Battery Mode 94.5%
Battery - Standard Model
Battery Type 12V9AH
Quantity (16+16) pcs
Typical Recharge Time 9 Hours recover to 90% capacity
Charging Current (max.) 1A-12A (Adjustable)
Charging Voltage ± 218VDC ±10%
Battery - Extended Runtime Model
Battery Type Depending on the capacity of external batteries
Quantity 32 (16+16pcs) ~ 40(20+20pcs) Adjustable
Charging Current (max.) 1A-12A (Adjustable)
Charging Voltage ± 13.65V x N (N=16~20)
Galleon Pro III 60K
Phase 3 phase in / 3 phase out
Capacity 60kVA / 60kW
Input
Nominal Voltage Three Phase 3 x 380V / 400V / 415V (4 Wires, 3 Phases + N + E)
Voltage Range -30% ~ +20%
Frequency Range 40Hz ~ 70Hz
Power Factor >0.99 @ 100% load
Total Current Harmonic Distortion < 3% at full load
Output
Output Voltage Three Phase 3 x 360V* / 380V / 400V / 415V (4 Wires, 3 Phases + N + E)
AC Voltage Regulation (Batt. Mode) ± 1%
Frequency Range (Sync. Range) 46Hz~54Hz or 56~64Hz
Frequency Range (Batt. Mode) ± 1%
Current Crest Ratio 3:1 (max)
Harmonic Distortion < 1% THD (Linear load)
< 3% THD (Non-linear load)
Transfer Time - AC Mode to Battery Mode 0ms
Transfer Time - Inverter to Bypass 0ms
Waveform (Battery mode) Pure Sinewave
Overload Capability 100~110% for 60mins; 111~125% for 10mins; 126~150% for 1min;
>150% for 400ms
Bypass
Input Nominal Voltage Three Phase 3 x 380V / 400V / 415V (3 Phases + N)
Input Voltage Range -30% ~ +20%
Frequency Range (Synchronized) 46Hz~54Hz or 56~64Hz
Overload Capability >150% for 1min (default), continuously working until break protection cuts off (optional)
Efficiency
AC Mode 95.5%
ECO Mode 99.0%
Battery Mode 96.0%
Battery - Standard Model
Battery Type 12V Sealed Lead Acid Maintenance Free (SLA)
Quantity 32~40 pcs User Adjustable, 3 poles (Positive, Mid-Point, Negative)
Typical Recharge Time 9 Hours recover to 90% capacity
Charging Current (max.) 1A-18A (Adjustable)
Charging Voltage 13.7Vdc ± 10% x N [N = 16 ~ 20]
Standard
Safety EN-62040-1-2; EN-60950-1
Electromagnetic Compatibility (EMC) EN-61000-2; EN-61000-4
Operating VFI-SS-111 in accordance with EN62040-3
Design CE
Galleon Pro III 100KS
Phase 3 phase in / 3 phase out
Capacity 100kVA / 100kW
Input
Nominal Voltage Three Phase 3 x 380V / 400V / 415V (4 Wires, 3 Phases + N + E)
Voltage Range -30% ~ +20%
Frequency Range 40Hz ~ 70Hz
Power Factor >0.99 @ 100% load
Total Current Harmonic Distortion < 3% at full load
Output
Output Voltage Three Phase 3 x 360V* / 380V / 400V / 415V (4 Wires, 3 Phases + N + E)
AC Voltage Regulation (Batt. Mode) ± 1%
Frequency Range (Sync. Range) 46Hz~54Hz or 56~64Hz
Frequency Range (Batt. Mode) ± 1%
Current Crest Ratio 3:1 (max)
Harmonic Distortion < 1% THD (Linear load)
< 3% THD (Non-linear load)
Transfer Time - AC Mode to Battery Mode 0ms
Transfer Time - Inverter to Bypass 0ms
Waveform (Battery mode) Pure Sinewave
Overload Capability 100~110% for 60mins; 111~125% for 10mins; 126~150% for 1min;
>150% for 400ms
Bypass
Input Nominal Voltage Three Phase 3 x 380V / 400V / 415V (3 Phases + N)
Input Voltage Range -30% ~ +20%
Frequency Range (Synchronized) 46Hz~54Hz or 56~64Hz
Overload Capability >150% for 1min (default), continuously working until break protection cuts off (optional)
Efficiency
AC Mode 95.5%
ECO Mode 99.0%
Battery Mode 96.0%
Battery - Standard Model
Battery Type 12V Sealed Lead Acid Maintenance Free (SLA)
Quantity 32~40 pcs User Adjustable, 3 poles (Positive, Mid-Point, Negative)
Typical Recharge Time 9 Hours recover to 90% capacity
Charging Current (max.) 2A-36A (Adjustable)
Charging Voltage 13.7Vdc ± 10% x N [N = 16 ~ 20]
Standard
Safety EN-62040-1-2; EN-60950-1
Electromagnetic Compatibility (EMC) EN-61000-2; EN-61000-4
Operating VFI-SS-111 in accordance with EN62040-3
Design CE
Galleon Pro III 120KS
Phase 3 phase in / 3 phase out
Capacity 120kVA / 120kW
Input
Nominal Voltage Three Phase 3 x 380V / 400V / 415V (4 Wires, 3 Phases + N + E)
Voltage Range -30% ~ +20%
Frequency Range 40Hz ~ 70Hz
Power Factor >0.99 @ 100% load
Total Current Harmonic Distortion < 3% at full load
Output
Output Voltage Three Phase 3 x 360V* / 380V / 400V / 415V (4 Wires, 3 Phases + N + E)
AC Voltage Regulation (Batt. Mode) ± 1%
Frequency Range (Sync. Range) 46Hz~54Hz or 56~64Hz
Frequency Range (Batt. Mode) ± 1%
Current Crest Ratio 3:1 (max)
Harmonic Distortion < 1% THD (Linear load)
< 3% THD (Non-linear load)
Transfer Time - AC Mode to Battery Mode 0ms
Transfer Time - Inverter to Bypass 0ms
Waveform (Battery mode) Pure Sinewave
Overload Capability 100~110% for 60mins; 111~125% for 10mins; 126~150% for 1min;
>150% for 400ms
Bypass
Input Nominal Voltage Three Phase 3 x 380V / 400V / 415V (3 Phases + N)
Input Voltage Range -30% ~ +20%
Frequency Range (Synchronized) 46Hz~54Hz or 56~64Hz
Overload Capability >150% for 1min (default), continuously working until break protection cuts off (optional)
Efficiency
AC Mode 95.5%
ECO Mode 99.0%
Battery Mode 96.0%
Battery - Standard Model
Battery Type 12V Sealed Lead Acid Maintenance Free (SLA)
Quantity 32~40 pcs User Adjustable, 3 poles (Positive, Mid-Point, Negative)
Typical Recharge Time 9 Hours recover to 90% capacity
Charging Current (max.) 2A-36A (Adjustable)
Charging Voltage 13.7Vdc ± 10% x N [N = 16 ~ 20]
Standard
Safety EN-62040-1-2; EN-60950-1
Electromagnetic Compatibility (EMC) EN-61000-2; EN-61000-4
Operating VFI-SS-111 in accordance with EN62040-3
Design CE
Galleon Pro III 160KS
Phase 3 phase in / 3 phase out
Capacity 160kVA / 160kW
Input
Nominal Voltage Three Phase 3 x 380V / 400V / 415V (4 Wires, 3 Phases + N + E)
Voltage Range -30% ~ +20%
Frequency Range 40Hz ~ 70Hz
Power Factor >0.99 @ 100% load
Total Current Harmonic Distortion < 3% at full load
Output
Output Voltage Three Phase 3 x 360V* / 380V / 400V / 415V (4 Wires, 3 Phases + N + E)
AC Voltage Regulation (Batt. Mode) ± 1%
Frequency Range (Sync. Range) 46Hz~54Hz or 56~64Hz
Frequency Range (Batt. Mode) ± 1%
Current Crest Ratio 3:1 (max)
Harmonic Distortion < 1% THD (Linear load)
< 3% THD (Non-linear load)
Transfer Time - AC Mode to Battery Mode 0ms
Transfer Time - Inverter to Bypass 0ms
Waveform (Battery mode) Pure Sinewave
Overload Capability 100~110% for 60mins; 111~125% for 10mins; 126~150% for 1min;
>150% for 400ms
Bypass
Input Nominal Voltage Three Phase 3 x 380V / 400V / 415V (3 Phases + N)
Input Voltage Range -30% ~ +20%
Frequency Range (Synchronized) 46Hz~54Hz or 56~64Hz
Overload Capability >150% for 1min (default), continuously working until break protection cuts off (optional)
Efficiency
AC Mode 95.5%
ECO Mode 99.0%
Battery Mode 96.0%
Battery - Standard Model
Battery Type 12V Sealed Lead Acid Maintenance Free (SLA)
Quantity 32~40 pcs User Adjustable, 3 poles (Positive, Mid-Point, Negative)
Typical Recharge Time 9 Hours recover to 90% capacity
Charging Current (max.) 3A-54A (Adjustable)
Charging Voltage 13.7Vdc ± 10% x N [N = 16 ~ 20]
Standard
Safety EN-62040-1-2; EN-60950-1
Electromagnetic Compatibility (EMC) EN-61000-2; EN-61000-4
Operating VFI-SS-111 in accordance with EN62040-3
Design CE
Galleon Pro III 180KS
Phase 3 phase in / 3 phase out
Capacity 180kVA / 180kW
Input
Nominal Voltage Three Phase 3 x 380V / 400V / 415V (4 Wires, 3 Phases + N + E)
Voltage Range -30% ~ +20%
Frequency Range 40Hz ~ 70Hz
Power Factor >0.99 @ 100% load
Total Current Harmonic Distortion < 3% at full load
Output
Output Voltage Three Phase 3 x 360V* / 380V / 400V / 415V (4 Wires, 3 Phases + N + E)
AC Voltage Regulation (Batt. Mode) ± 1%
Frequency Range (Sync. Range) 46Hz~54Hz or 56~64Hz
Frequency Range (Batt. Mode) ± 1%
Current Crest Ratio 3:1 (max)
Harmonic Distortion < 1% THD (Linear load)
< 3% THD (Non-linear load)
Transfer Time - AC Mode to Battery Mode 0ms
Transfer Time - Inverter to Bypass 0ms
Waveform (Battery mode) Pure Sinewave
Overload Capability 100~110% for 60mins; 111~125% for 10mins; 126~150% for 1min;
>150% for 400ms
Bypass
Input Nominal Voltage Three Phase 3 x 380V / 400V / 415V (3 Phases + N)
Input Voltage Range -30% ~ +20%
Frequency Range (Synchronized) 46Hz~54Hz or 56~64Hz
Overload Capability >150% for 1min (default), continuously working until break protection cuts off (optional)
Efficiency
AC Mode 95.5%
ECO Mode 99.0%
Battery Mode 96.0%
Battery - Standard Model
Battery Type 12V Sealed Lead Acid Maintenance Free (SLA)
Quantity 32~40 pcs User Adjustable, 3 poles (Positive, Mid-Point, Negative)
Typical Recharge Time 9 Hours recover to 90% capacity
Charging Current (max.) 3A-54A (Adjustable)
Charging Voltage 13.7Vdc ± 10% x N [N = 16 ~ 20]
Standard
Safety EN-62040-1-2; EN-60950-1
Electromagnetic Compatibility (EMC) EN-61000-2; EN-61000-4
Operating VFI-SS-111 in accordance with EN62040-3
Design CE
Galleon Pro III 200KS
Phase 3 phase in / 3 phase out
Capacity 200kVA / 200kW
Input
Nominal Voltage Three Phase 3 x 380V / 400V / 415V (4 Wires, 3 Phases + N + E)
Voltage Range -30% ~ +20%
Frequency Range 40Hz ~ 70Hz
Power Factor >0.99 @ 100% load
Total Current Harmonic Distortion < 3% at full load
Output
Output Voltage Three Phase 3 x 360V* / 380V / 400V / 415V (4 Wires, 3 Phases + N + E)
AC Voltage Regulation (Batt. Mode) ± 1%
Frequency Range (Sync. Range) 46Hz~54Hz or 56~64Hz
Frequency Range (Batt. Mode) ± 1%
Current Crest Ratio 3:1 (max)
Harmonic Distortion < 1% THD (Linear load)
< 3% THD (Non-linear load)
Transfer Time - AC Mode to Battery Mode 0ms
Transfer Time - Inverter to Bypass 0ms
Waveform (Battery mode) Pure Sinewave
Overload Capability 100~110% for 60mins; 111~125% for 10mins; 126~150% for 1min;
>150% for 400ms
Bypass
Input Nominal Voltage Three Phase 3 x 380V / 400V / 415V (3 Phases + N)
Input Voltage Range -30% ~ +20%
Frequency Range (Synchronized) 46Hz~54Hz or 56~64Hz
Overload Capability >150% for 1min (default), continuously working until break protection cuts off (optional)
Efficiency
AC Mode 95.5%
ECO Mode 99.0%
Battery Mode 96.0%
Battery - Standard Model
Battery Type 12V Sealed Lead Acid Maintenance Free (SLA)
Quantity 32~40 pcs User Adjustable, 3 poles (Positive, Mid-Point, Negative)
Typical Recharge Time 9 Hours recover to 90% capacity
Charging Current (max.) 3A-54A (Adjustable)
Charging Voltage 13.7Vdc ± 10% x N [N = 16 ~ 20]
Standard
Safety EN-62040-1-2; EN-60950-1
Electromagnetic Compatibility (EMC) EN-61000-2; EN-61000-4
Operating VFI-SS-111 in accordance with EN62040-3
Design CE

Technical specifications are subject to change without notice.
*When output voltage is set to 3 x 360VAC, the output power shall be de-rated to 90%.