Preloader
Galleon Pro Series
Double Conversion On-line Parallel System from 1KVA to 10KVA
Galleon Pro Series
Features

Features

  • True Double-Conversion Online Line Sinewave UPS
  • Wide input voltage range (110 V - 300 V)
  • Programmable power management outlets
  • 50/60 Hz Frequency Converter Mode
  • ECO mode operation for energy saving
  • Emergency Power Off (EPO) Function
  • SNMP+USB+RS+232 multiple communications
  • Smart battery charger design to optimize battery performance
  • DSP technology applied for 6K and up models
  • Maintenance bypass available for 6K and up models
  • Optional N+X parallel redundancy available for 6K and up models
  • Adjustable battery numbers for 6K and up models
  • Built-in isolation transformer (Option)
Galleon Pro 1K/1KS
Phase Single phase with ground
Capacity 1000VA / 900W
Input
Nominal Voltage 100/110/115/120/127 VAC or 200/206/220/230/240 VAC
Voltage Range 55-150 VAC ± 5% or 100-300 VAC ± 5% @ 50% load
80-150 VAC ± 5% or 160-300 VAC ± 5% @ 100% load
Frequency Range 40Hz - 70Hz
Power Factor > 0.99 @ Nominal Voltage @ 100% load
THDi < 5% @ 100 ~ 130 VAC or 205 -245 VAC
< 1.6% at input and full linear load condition with battery fully charged
Output
Voltage Range 100/110/115/120/127 VAC or 200/206/220/230/240 VAC
AC Voltage Regulation (Batt. Mode) ± 1%
Frequency Range (Sync. Range) 47Hz ~ 53Hz or 57~63Hz
Frequency Range (Batt. Mode) 50Hz ± 0.25Hz or 60Hz ± 0.3Hz
Current Crest Ratio 3:1
Harmonic Distortion < 2% THD (Linear Load)
< 4% THD (Non-linear Load)
Transfer Time - AC Mode to Battery Mode 0ms
Transfer Time - Inverter to Bypass 4ms (Typical)
Waveform (Battery mode) Pure Sinewave
Efficiency
AC Mode 85%
Battery Mode 83%
Battery - Standard Model
Battery Type 12V 7AH
Quantity 3
Typical Recharge Time 4 Hours recover to 90% capacity
Charging Current (max.) 1A
Charging Voltage 41.0 VDC ± 1%
Battery - Extended Runtime Model
Battery Type Depending on applications
Quantity 3
Charging Current (max.) Selectable via LCD/front panel setting (1A/2A/4A/6A/8A)
Charging Voltage 41.0 ± 1%
Galleon Pro 1K5/1K5S
Phase Single phase with ground
Capacity 1500VA / 1350W
Input
Nominal Voltage 100/110/115/120/127 VAC or 200/206/220/230/240 VAC
Voltage Range 55-150 VAC ± 5% or 100-300 VAC ± 5% @ 50% load
80-150 VAC ± 5% or 160-300 VAC ± 5% @ 100% load
Frequency Range 40Hz - 70Hz
Power Factor > 0.99 @ Nominal Voltage @ 100% load
THDi < 5% @ 100 ~ 130 VAC or 205 -245 VAC
< 1.6% at input and full linear load condition with battery fully charged
Output
Voltage Range 100/110/115/120/127 VAC or 200/206/220/230/240 VAC
AC Voltage Regulation (Batt. Mode) ± 1%
Frequency Range (Sync. Range) 47Hz ~ 53Hz or 57~63Hz
Frequency Range (Batt. Mode) 50Hz ± 0.25Hz or 60Hz ± 0.3Hz
Current Crest Ratio 3:1
Harmonic Distortion < 2% THD (Linear Load)
< 4% THD (Non-linear Load)
Transfer Time - AC Mode to Battery Mode 0ms
Transfer Time - Inverter to Bypass 4ms (Typical)
Waveform (Battery mode) Pure Sinewave
Efficiency
AC Mode 85%
Battery Mode 83%
Battery - Standard Model
Battery Type 12V 9AH
Quantity 3
Typical Recharge Time 4 Hours recover to 90% capacity
Charging Current (max.) 1A
Charging Voltage 41.0 VDC ± 1%
Battery - Extended Runtime Model
Battery Type Depending on applications
Quantity 3
Charging Current (max.) Selectable via LCD/front panel setting (1A/2A/4A/6A/8A)
Charging Voltage 41.0 ± 1%
Galleon Pro 2K/2KS
Phase Single phase with ground
Capacity 2000VA / 1800W
Input
Nominal Voltage 100/110/115/120/127 VAC or 200/206/220/230/240 VAC
Voltage Range 55-150 VAC ± 5% or 100-300 VAC ± 5% @ 50% load
80-150 VAC ± 5% or 160-300 VAC ± 5% @ 100% load
Frequency Range 40Hz - 70Hz
Power Factor > 0.99 @ Nominal Voltage @ 100% load
THDi < 5% @ 100 ~ 130 VAC or 205 -245 VAC
< 1.6% at input and full linear load condition with battery fully charged
Output
Voltage Range 100/110/115/120/127 VAC or 200/206/220/230/240 VAC
AC Voltage Regulation (Batt. Mode) ± 1%
Frequency Range (Sync. Range) 47Hz ~ 53Hz or 57~63Hz
Frequency Range (Batt. Mode) 50Hz ± 0.25Hz or 60Hz ± 0.3Hz
Current Crest Ratio 3:1
Harmonic Distortion < 2% THD (Linear Load)
< 4% THD (Non-linear Load)
Transfer Time - AC Mode to Battery Mode 0ms
Transfer Time - Inverter to Bypass 4ms (Typical)
Waveform (Battery mode) Pure Sinewave
Efficiency
AC Mode 88%
Battery Mode 83%
Battery - Standard Model
Battery Type 12V 7AH
Quantity 6
Typical Recharge Time 4 Hours recover to 90% capacity
Charging Current (max.) 1A
Charging Voltage 82.1 VDC ± 1%
Battery - Extended Runtime Model
Battery Type Depending on applications
Quantity 6
Charging Current (max.) Selectable via LCD/front panel setting (1A/2A/4A/6A/8A)
Charging Voltage 82.1 ± 1%
Galleon Pro 3K/3KS
Phase Single phase with ground
Capacity 3000VA / 2700W
Input
Nominal Voltage 100/110/115/120/127 VAC or 200/206/220/230/240 VAC
Voltage Range 55-150 VAC ± 5% or 100-300 VAC ± 5% @ 50% load
80-150 VAC ± 5% or 160-300 VAC ± 5% @ 100% load
Frequency Range 40Hz - 70Hz
Power Factor > 0.99 @ Nominal Voltage @ 100% load
THDi < 5% @ 100 ~ 130 VAC or 205 -245 VAC
< 1.6% at input and full linear load condition with battery fully charged
Output
Voltage Range 100/110/115/120/127 VAC or 200/206/220/230/240 VAC
AC Voltage Regulation (Batt. Mode) ± 1%
Frequency Range (Sync. Range) 47Hz ~ 53Hz or 57~63Hz
Frequency Range (Batt. Mode) 50Hz ± 0.25Hz or 60Hz ± 0.3Hz
Current Crest Ratio 3:1
Harmonic Distortion < 2% THD (Linear Load)
< 4% THD (Non-linear Load)
Transfer Time - AC Mode to Battery Mode 0ms
Transfer Time - Inverter to Bypass 4ms (Typical)
Waveform (Battery mode) Pure Sinewave
Efficiency
AC Mode 88%
Battery Mode 83%
Battery - Standard Model
Battery Type 12V 9AH
Quantity 6
Typical Recharge Time 4 Hours recover to 90% capacity
Charging Current (max.) 1A
Charging Voltage 41.0 VDC ± 1%
Battery - Extended Runtime Model
Battery Type Depending on applications
Quantity 6
Charging Current (max.) Selectable via LCD/front panel setting (1A/2A/4A/6A/8A)
Charging Voltage 82.1 ± 1%
Galleon Pro 6K/6KS
Phase Single phase with ground
Capacity 6000VA / 6000W
Input
Nominal Voltage 208/220/230/240 VAC
Voltage Range 110-300 VAC @ 50% load
176-300 VAC @ 100% load
Frequency Range 46Hz - 54Hz or 56Hz - 64Hz
Power Factor > 0.99 @ Nominal Voltage @ 100% load
THDi < 5% @ 205-245 VAC
Output
Voltage Range 208/220/230/240 VAC
AC Voltage Regulation (Batt. Mode) ± 1%
Frequency Range (Sync. Range) 46Hz ~ 54Hz or 56~64Hz
Frequency Range (Batt. Mode) 50Hz ± 0.1Hz or 60Hz ± 0.1Hz
Current Crest Ratio 3:1
Harmonic Distortion < 3% THD (Linear Load)
< 6% THD (Non-linear Load)
Transfer Time - AC Mode to Battery Mode 0ms
Transfer Time - Inverter to Bypass 0ms
Waveform (Battery mode) Pure Sinewave
Efficiency
AC Mode 89%
Battery Mode 88%
Battery - Standard Model
Battery Type 12V 7AH
Quantity 20
Typical Recharge Time 7 Hours recover to 90% capacity
Charging Current (max.) 1A
Charging Voltage 273.0 VDC ± 1%
Battery - Extended Runtime Model
Battery Type Depending on applications
Quantity 18-20
Charging Current (max.) 4A
Charging Voltage 273.0 VDC ± 1%
Galleon Pro 10K/10KS
Phase Single phase with ground
Capacity 10000VA / 10000W
Input
Nominal Voltage 208/220/230/240 VAC
Voltage Range 110-300 VAC @ 50% load
176-300 VAC @ 100% load
Frequency Range 46Hz - 54Hz or 56Hz - 64Hz
Power Factor > 0.99 @ Nominal Voltage @ 100% load
THDi < 5% @ 205-245 VAC
Output
Voltage Range 208/220/230/240 VAC
AC Voltage Regulation (Batt. Mode) ± 1%
Frequency Range (Sync. Range) 46Hz ~ 54Hz or 56~64Hz
Frequency Range (Batt. Mode) 50Hz ± 0.1Hz or 60Hz ± 0.1Hz
Current Crest Ratio 3:1
Harmonic Distortion < 3% THD (Linear Load)
< 6% THD (Non-linear Load)
Transfer Time - AC Mode to Battery Mode 0ms
Transfer Time - Inverter to Bypass 0ms
Waveform (Battery mode) Pure Sinewave
Efficiency
AC Mode 89%
Battery Mode 88%
Battery - Standard Model
Battery Type 12V 9AH
Quantity 20
Typical Recharge Time 9 Hours recover to 90% capacity
Charging Current (max.) 1A
Charging Voltage 273.0 VDC ± 1%
Battery - Extended Runtime Model
Battery Type Depending on applications
Quantity 18-20
Charging Current (max.) 4A
Charging Voltage 273.0 VDC ± 1%

Technical specifications are subject to change without notice.